PP Duct Fittings: Types, Sizes, and Selection Guide

PP Duct Fittings: Types, Sizes, and Selection Guide

PP duct fittings are molded or fabricated polypropylene components — elbows, tees, reducers, wyes, flanges, dampers, and access doors — that connect and control straight duct sections in corrosive exhaust ventilation systems. The correct selection of PP duct fittings determines the system pressure drop, installation cost, and long-term reliability of the entire ductwork system. A poorly chosen fitting — a short-radius elbow instead of long-radius, or a 90-degree tee branch instead of 45-degree — can increase the system pressure drop by 50 to 100 percent and require a larger fan motor. This guide covers the available fitting types, material options, size ranges, pressure drop characteristics, flange and gasket specifications, damper types, access door requirements, and selection criteria for PP duct fittings in chemical exhaust service. For overall duct system design methodology, see our PP ductwork ventilation system design guide.

Key Takeaways

  • PP duct fittings are available in injection-molded (φ20-500 mm, tighter tolerances, lower cost) and fabricated (φ63-1,200 mm, any geometry, higher cost) versions. Select injection-molded for standard sizes and fabricated for non-standard dimensions.
  • Elbow radius selection directly affects system pressure drop — a short-radius elbow (R=1.0D) has 50-100% higher friction loss than long-radius (R=1.5D-2.0D). Use R=2.0D whenever space permits.
  • A 45-degree tee branch has 60 to 70 percent lower pressure drop than a 90-degree tee branch — specify 45-degree branch tees for all main duct takeoffs where flow efficiency matters.
  • Reducer taper should not exceed 15 degrees — a steeper taper creates turbulence and vibration that increases pressure drop by 30 to 50 percent and can damage the duct joint over time.
  • Access doors are required every 50 ft of straight run and at every change of direction per DVS 2205 — omitting access doors makes future inspection and cleaning impossible without cutting into the duct.

Standard PP Duct Fittings

Elbows: 45-Degree and 90-Degree

PP duct elbows are available in three radius classes: short radius (R=1.0 × duct diameter), standard radius (R=1.5 × diameter), and long radius (R=2.0 × diameter). Injection-molded elbows are typically produced in 45° and 90° configurations for diameters from 63 to 500 mm with R=1.5D as standard. Fabricated elbows are available for all diameters up to 1,200 mm with any radius specified by the designer. The pressure drop equivalent length for a 90° elbow varies significantly with radius: short radius R=1.0D adds 0.8 to 1.2 in. W.G. equivalent per elbow, R=1.5D adds 0.4 to 0.8 in. W.G., and R=2.0D adds 0.2 to 0.5 in. W.G. For a system with 10 elbows, specifying long-radius instead of short-radius reduces the total system pressure loss by 3.0 to 7.0 in. W.G. — enough to allow a fan motor one size smaller. When space is constrained, use two 45° elbows with a straight section between them instead of one 90° short-radius elbow — the pressure drop of two 45° elbows plus the straight section is 20 to 30 percent lower than one 90° short-radius elbow. All PP elbows must include a weld bead or gasket groove at both ends to match the joint method used for the straight duct sections.

Tees: Branch Angle Selection

PP duct tees are used where a branch duct connects to a main duct. The branch angle is the most important selection parameter: a 45-degree branch tee has an equivalent length of 0.5 to 1.0 in. W.G. per fitting, while a 90-degree branch tee has 1.5 to 2.5 in. W.G. — 200 to 300 percent higher. A PP ductwork system with 8 branch tees can save 8.0 to 12.0 in. W.G. of total system pressure by specifying 45-degree branch tees instead of 90-degree, which reduces the fan motor size by 15 to 25 HP for a typical 10,000 CFM system. Tees are also available with a gradual radius at the branch-to-main intersection (radiused-entry tee) that reduces the pressure drop by an additional 20 to 30 percent compared to a sharp-entry tee. Specify 45-degree radiused-entry tees for all main duct takeoffs and reserve 90-degree tees for low-flow branches and short runs where the pressure drop penalty is acceptable. The centerline branch diameter can be the same as the main or reduced — specify reducing tees where the branch flow is less than the main flow. Internal guide vanes are available for large-diameter tees above 600 mm to reduce the turbulence at the branch intersection.

Reducers: Concentric vs Eccentric

PP duct reducers transition between two different duct diameters. The taper angle must not exceed 15 degrees — a reducer from 24 inches to 18 inches must be at least 24 inches long. Steeper angles create flow separation and turbulence that increases pressure drop by 30 to 50 percent and generates vibration at blade passage frequency (matching the fan impeller frequency) that can cause duct joint failure in 2 to 4 years. Concentric reducers have the centerline aligned and are used in vertical duct runs where condensate drainage is not required. Eccentric reducers have the bottom or top surface aligned — bottom-flat eccentric reducers are used in horizontal duct runs to prevent condensate accumulation at the step, which is critical for chemical exhaust systems handling saturated or condensing gas streams. Specify eccentric reducers with the flat side on the bottom for all horizontal PP ductwork in chemical service — condensate pooling at a concentric reducer’s step causes PP degradation at the water line over 3 to 5 years if the condensate absorbs acid gases from the exhaust stream. Per ASTM D4101, PP duct fittings must be fabricated from the same material grade and lot as the straight duct sections to ensure uniform chemical resistance and weld compatibility.

PP Duct Fitting Sizes and Standard Dimensions

PP duct fittings are manufactured in standard nominal diameters matching the PP straight duct sizes. Injection-molded fittings cover diameters from 20 mm to 500 mm (0.75 to 20 inches) with a single-piece construction that provides uniform wall thickness matching the straight duct wall for each diameter. Fabricated fittings cover the full range from 63 mm to 1,200 mm (2.5 to 48 inches) using PP sheet that is cut, formed, and welded — the fabricated fitting wall thickness matches the straight duct wall thickness for the corresponding diameter. The table below shows standard diameters and the corresponding wall thickness for PP duct fittings at standard pressure rating (-500 to +2,000 Pa).

Nominal Diameter PPN (mm) Wall Thickness (mm) Fitting Type Available
20-50 mm (0.75-2 in.) 20, 25, 32, 40, 50 2.0-2.5 Elbow, Tee, Reducer — injection molded
63-160 mm (2.5-6 in.) 63, 75, 90, 110, 160 3.0 All — injection molded
200-315 mm (8-12 in.) 200, 250, 315 4.0 All — injection molded or fabricated
355-500 mm (14-20 in.) 355, 400, 450, 500 5.0 All — injection molded or fabricated
560-800 mm (22-32 in.) 560, 630, 710, 800 6.0-8.0 All — fabricated only
900-1,200 mm (36-48 in.) 900, 1,000, 1,200 8.0-10.0 All — fabricated only

The standard PP duct fittings are available in the following configurations per diameter range. Elbows: 45° and 90°, R=1.5D standard, R=2.0D on request for fabricated sizes above 200 mm. Tees: equal (all ports same diameter) and reducing (branch smaller than main), 45° branch and 90° branch. Reducers: concentric and eccentric (bottom-flat for horizontal runs), taper angle maximum 15°. Wyes: 45° Y-branch standard, 60° on request. Flanges: ANSI B16.5 Class 150 drilling pattern, with backing ring required above 600 mm diameter. For non-standard diameters between the listed sizes — for example, a 14-inch diameter fitting where the metric equivalent is 355 mm — specify fabricated fittings because injection molds are only available for the standard metric diameters listed. The diameter selection in a PP ductwork ventilation system design should use these standard fitting sizes to avoid the 1.5 to 3.0 times cost premium for non-standard fabricated fittings.

PP Duct Flanges and Connection Types

PP Flange Dimensions and Drilling Patterns

PP flanges connect duct sections that require disassembly for maintenance — at fan connections, scrubber nozzles, and major branch points. The flange dimensions follow ANSI B16.5 Class 150 drilling patterns for PP-to-PP connections or ASME B16.5 Class 150 for PP-to-steel connections. A 24-inch PP flange has a bolt circle of 27.25 inches with 24 bolt holes of 0.75-inch diameter for 5/8-inch bolts. The flange thickness for PP increases with diameter: 10 mm for ducts up to 250 mm, 12 mm for 300 to 600 mm, and 15 mm for 700 to 1,200 mm. All flanges include a recessed gasket groove 3 mm deep and 5 mm wide on the sealing face to locate the gasket during assembly — without the groove, the gasket shifts during bolt tightening and creates a leak path. The flange ring is extrusion-welded to the duct end using PP filler rod, with a 45-degree fillet weld on both the inside and outside of the joint.

Backing Rings vs All-PP Flanges

For duct diameters above 600 mm, all-PP flanges require backing rings to prevent the PP flange from bowing between the bolts under the specified torque. The backing ring is a split ring fabricated from SS 304 or FRP, 5 to 8 mm thick, that sandwiches the PP flange between the ring and the bolt washer. Backing rings add $50 to $150 per flange but prevent the PP flange from cold-flowing under sustained bolt load — without backing rings, an all-PP flange above 600 mm relaxes the bolt torque by 30 to 50 percent over 6 to 12 months, causing the gasket to leak. For diameters up to 600 mm, all-PP flanges without backing rings are adequate if the bolts are torqued to the manufacturer’s specification (15 to 25 ft-lb for 3/8-inch bolts) and retorqued at 6-month intervals. Specify full-face gaskets (1/8-inch compressed Viton for general chemical service or PTFE for aggressive chemical service) for all PP flanged connections. Never use full-face rubber gaskets — rubber degrades within 12 months in chemical exhaust service, and the degraded gasket material can be drawn into the duct and damage downstream equipment.

PP Duct Dampers

Manual Balancing Dampers

Manual balancing dampers are installed at each branch takeoff in a multi-branch PP duct system to adjust airflow distribution. The damper consists of a PP flanged spool piece containing a rotating PP blade that pivots from fully open (0 degrees, parallel to airflow) to fully closed (90 degrees, perpendicular to airflow). The blade is connected to a SS 316 shaft that extends through the damper housing to an external locking handle with position indicator. Manual dampers are adjusted during system commissioning to balance airflow to each branch and then locked in position. The pressure drop across a fully open balancing damper is 0.05 to 0.15 in. W.G. — negligible for system design purposes. A partially closed damper at 30 to 60 degrees creates 0.5 to 3.0 in. W.G. of additional resistance used for balancing. The damper must be located at least 3 duct diameters downstream of any fitting to ensure uniform airflow velocity across the damper blade — a damper placed too close to an elbow reads a non-uniform velocity profile and cannot be accurately set.

Motorized Isolation Dampers

Motorized dampers are used where automatic isolation or remote control of PP duct branches is required — fire isolation, emergency exhaust shutdown, or automated system balancing. The motorized damper uses the same PP housing and SS 316 shaft as the manual version, with a spring-return (fail-safe) actuator mounted externally. The actuator torque must be sized for the PP blade weight and the friction of the SS 316 shaft in the PP bearing surface — a 24-inch damper blade requires 50 to 100 in-lb of actuator torque. Specify spring-return actuators that close the damper on power loss (normally closed for fire isolation) or open the damper on power loss (normally open for emergency exhaust). The actuator enclosure must be NEMA 4X for outdoor chemical installations or NEMA 12 for indoor clean environments. Do not mount the actuator inside the duct — the actuator is not corrosion-resistant and fails within 6 to 12 months if exposed to chemical exhaust.

Backdraft Dampers

Backdraft dampers prevent exhaust flow from reversing through an idle branch when other branches are operating. They are installed at the discharge of each fan where multiple fans discharge into a common header, or at each branch takeoff where the system pressure could push flow backward through an inactive branch. The backdraft damper consists of a PP frame with gravity-hinged PP or SS blades that open by airflow pressure and close by gravity when flow stops. The blades must be light enough to open at 0.1 to 0.2 in. W.G. of differential pressure and heavy enough to close fully against 0.5 in. W.G. of back pressure. For dampers in systems that handle condensable vapors, specify SS blades instead of PP because the blade edges in backdraft dampers must be straight and parallel — PP blades warp over time in condensing service and lose the ability to seal closed, allowing backdraft leakage of 20 to 50 percent of the branch flow.

Access Doors and Inspection Ports

PP ductwork requires access doors at every change of direction (elbow or tee), every 50 ft of straight run, and immediately upstream of every damper. The access door provides entry for visual inspection, cleaning, and blockage removal. Without access doors, a blocked duct cannot be cleared without cutting into the PP and welding a patch, which costs $200 to $500 per incident and leaves a weld joint that is a potential leak point. The standard access door for PP ductwork is a 12 × 12 inch opening for ducts up to 18 inches in diameter, and 18 × 18 inches for larger ducts. The door is a PP frame extrusion-welded to the duct wall, with a PP or SS 316 door panel sealed with a 1/8-inch Viton gasket and secured by SS 316 swing bolts. Quick-open access doors — with cam-lock handles instead of swing bolts — are available for locations where frequent inspection is planned (every 3 months or more). Quick-open doors cost 30 to 50 percent more than bolt-on doors but reduce inspection time from 15 minutes to 2 minutes per door. For a system with 10 access doors inspected quarterly, the annual labor saving from quick-open doors is 8.7 hours — $260 per year at $30/hour labor rate.

Inspection ports — 4-inch diameter PP threaded caps that screw into PP weld couplings installed in the duct wall — are required at each branch takeoff and at the fan inlet and discharge connections. The inspection port cap is removed to insert a pitot tube for airflow measurement during system balancing or to insert a boroscope camera for visual inspection. The inspection port must be located at least 3 duct diameters downstream of any fitting and 2 duct diameters upstream of any damper to ensure accurate airflow readings. For ducts larger than 600 mm, install two inspection ports at 90-degree separation (one at the top, one at the side) to allow pitot tube traverse measurements that capture the velocity profile across the duct cross-section. The inspection ports must be labeled with the station number on the outside of the duct — without labeling, technicians cannot locate the correct port during balancing, and they resort to drilling holes in the duct that must later be patched.

Fitting Pressure Drop Reference Table

The table below shows the equivalent straight duct length (in feet) for each fitting type by duct diameter. To calculate the total system pressure loss, add the equivalent length of each fitting to the actual straight duct length, then calculate the friction loss for the total equivalent length using the friction loss values for the corresponding duct diameter and velocity. These values are for fully developed turbulent flow in smooth PP duct at 2,000 ft/min velocity. For velocities significantly different from 2,000 ft/min, adjust the equivalent length by the ratio (V/2,000)².

Fitting Type 6 in. 10 in. 14 in. 18 in. 24 in. 30 in. 36 in.
90° elbow, R=1.0D 8 14 20 26 35 44 53
90° elbow, R=1.5D 5 9 13 17 23 29 35
90° elbow, R=2.0D 3 6 9 12 16 20 24
45° elbow, R=1.5D 3 5 8 10 14 18 22
Tee — 45° branch 10 18 25 33 44 55 66
Tee — 90° branch 25 40 55 70 90 115 140
Tee — straight flow 3 5 7 9 12 15 18
Reducer, ≤15° taper 2 4 6 8 10 13 16
Reducer, >15° taper 6 10 14 18 24 30 36
Balancing damper, open 2 4 5 7 9 12 14
Wye (Y-branch), 45° 6 10 15 19 26 33 40

Use the table above to estimate the total equivalent length of all fittings in a PP duct system. For a 30-inch diameter system with 6 long-radius elbows (R=1.5D), 4 tee 45° branches, and 2 balancing dampers, the total equivalent length from fittings is (6 × 29) + (4 × 55) + (2 × 12) = 174 + 220 + 24 = 418 ft. Add this to the actual straight duct length to get the total equivalent length for friction loss calculation. A complete PP ductwork ventilation system design uses this fitting data alongside the friction loss charts from the pillar guide to size the fan correctly. The difference between using all long-radius elbows (R=1.5D) versus all short-radius (R=1.0D) in a system with 12 elbows is 12 × (44 − 29) = 180 ft of equivalent length — enough to change the required fan motor size by 5 to 10 HP.

PP Duct Fitting Selection Guide

Selection Factor Injection-Molded Fitting Fabricated (Welded) Fitting
Size range φ20-500 mm standard φ63-1,200 mm custom
Tolerances ±0.5 mm (tight) ±2 mm (variable)
Wall thickness uniformity Excellent (molded) Variable (welded seams)
Minimum order quantity Single piece Single piece
Pressure drop (same geometry) Lower (smooth internal surfaces) Higher (weld bead internal projections)
Custom geometry available No (fixed mold) Yes (any angle, radius, transition)
Relative cost per fitting 1.0× (baseline) 1.5-3.0×
Lead time Stock to 1 week 2-4 weeks

Select injection-molded PP duct fittings for standard sizes between 63 mm and 500 mm where R=1.5D elbows and 45° branch tees meet the system requirements. Injection-molded PP duct fittings have smoother internal surfaces, tighter tolerances, and lower cost than fabricated fittings — a 250 mm 90° injection-molded elbow costs $5 to $15 versus $15 to $40 for a fabricated elbow. For large-diameter systems above 500 mm, fabricated PP duct fittings are the only option — specify long-radius (R=2.0D) fabricated elbows to minimize pressure drop and 45° branch tees to reduce turbulence. For flanges, use injection-molded flanges up to 500 mm and fabricated flanges with SS 304 backing rings above 600 mm. For dampers and access doors, all sizes are fabricated because these components require assembly that cannot be molded in a single piece. Per ASTM D4101, all PP duct fittings must be from virgin PP resin for consistent chemical resistance and weldability. For a complete PP ductwork ventilation system design that incorporates the correct PP duct fittings, see our PP ductwork design guide.

PP Duct Fitting Installation and Chemical Compatibility

Installation Best Practices by Fitting Type

Elbow installation: orient elbows so that the flow direction matches the directional arrow marked on injection-molded elbows or the weld seam orientation on fabricated elbows. A 90-degree elbow installed backward increases pressure drop by 30 to 50 percent because the flow separation point moves to the wrong side of the elbow. For fabricated elbows, the longitudinal weld seam should be on the outside of the curve — a seam on the inside of the curve creates a turbulence source at the point of maximum velocity. Tee installation: the branch connection must be oriented at an angle no greater than 45 degrees from the main duct axis for branches carrying more than 30 percent of the main flow. A tee installed with the branch at 90 degrees to the main creates flow separation that reduces branch flow by 20 to 40 percent below the design value. Reducer installation: eccentric reducers in horizontal runs must have the flat side on the bottom to prevent condensate pooling. Concentric reducers are only for vertical runs or dry gas service. For horizontal ducts handling saturated exhaust at relative humidity above 80 percent, always specify bottom-flat eccentric reducers — the condensate that forms in the duct collects at the reducer step in a concentric reducer and causes localized PP degradation.

Gasket Chemical Compatibility

The gasket material between PP flanges must be selected based on the chemical composition and temperature of the exhaust gas. Compressed Viton (FKM) is the standard gasket for general chemical exhaust service — it resists HCl, H₂SO₄ up to 70 percent, HNO₃ up to 30 percent, and all hydrocarbons, at temperatures up to 120°C. Viton costs $15 to $30 per square foot for 1/8-inch sheet and provides 5 to 8 year service life in chemical exhaust flange service before replacement. PTFE (Teflon) gaskets are required for concentrated sulfuric acid above 70 percent, for HF service, for nitric acid above 30 percent, and for all services above 120°C up to 200°C. PTFE costs $30 to $60 per square foot — 2 to 3 times the cost of Viton — but provides inert chemical resistance to all chemicals that PP ductwork handles. EPDM gaskets are acceptable for dilute acid service below 50°C at concentrations below 10 percent — EPDM costs $8 to $15 per square foot and is the economy option for non-critical service. Do not use natural rubber, neoprene, or nitrile gaskets with PP duct fittings — these materials degrade within 6 to 12 months in any acid gas environment, and the degraded gasket particles can be drawn into the exhaust stream and deposit on fan impellers or scrubber packing. Per ASTM D4101, the gasket material must be compatible with both the PP flange material and the chemical exhaust stream to prevent galvanic or chemical attack at the flange interface.

Cost Comparison: Injection-Molded vs Fabricated PP Fittings

Fitting Type Size Injection-Molded Fabricated Cost Ratio
90° elbow 250 mm $8-15 $18-40 2.3-2.7×
90° elbow 500 mm N/A (max mold 500mm) $45-80
Tee, equal 250 mm $12-25 $30-60 2.4-2.5×
Reducer 250 to 200 mm $8-15 $20-40 2.5-2.7×
Flange (Class 150) 250 mm $6-12 $15-30 2.5×
Balancing damper 250 mm N/A (assembly required) $40-80

The cost comparison shows that injection-molded PP duct fittings are 2.3 to 2.7 times less expensive than fabricated fittings for the same size and geometry. For a typical 10,000 CFM PP duct system with 15 elbows, 8 tees, 6 reducers, and 10 flanges at 250 mm diameter, the fitting cost difference between all injection-molded ($530 to $1,070) and all fabricated ($1,240 to $2,680) is $710 to $1,610 — a saving of 55 to 60 percent. The cost saving alone justifies specifying injection-molded PP duct fittings wherever the standard sizes and geometry meet the system requirements. Only specify fabricated fittings for diameters above 500 mm or where non-standard geometry (R=2.0D elbows, custom branch angles) is required for system performance.

Field Case: Fitting Selection Error in a Chemical Exhaust System

A specialty chemical manufacturer in Illinois installed a PP ductwork ventilation system on a mixed acid (HCl + H₂SO₄) exhaust system in 2021 with 24-inch diameter main duct and eight 12-inch branch ducts serving eight process tanks. The system designer specified 90-degree short-radius tees (R=1.0D, 90° branch) for all eight branches because the catalog showed they were $8 cheaper per tee than 45-degree long-radius tees — a total saving of $64 on fitting cost. After commissioning, airflow testing at the eight hoods showed branch flows ranging from 60 to 140 percent of the design 1,200 CFM — a wide imbalance caused by the turbulent flow at the 90-degree tee branches. The plant spent $3,200 on a balancing contractor who installed balancing dampers at each branch and spent 3 days adjusting the dampers to achieve uniform flow within ±15 percent. The total balancing cost — $3,200 — was 50 times the $64 saving on the tee selection.

The plant replaced the 90-degree short-radius tees with 45-degree radiused-entry tees during a scheduled maintenance shutdown in 2023 at a material cost of $1,600 (8 tees × $200 each for fabricated 45° tees) plus $1,800 installation labor. After replacement, the eight branches achieved balanced flow within ±5 percent without dampers, the total system pressure dropped by 2.8 in. W.G., and the fan motor amperage decreased from 28 A to 24 A — a 14 percent energy saving worth $1,150 per year at 6,000 operating hours. The $3,400 tee replacement cost had a payback period of 3.0 years from energy savings alone, not including the initial $3,200 balancing cost that was wasted because the 90-degree tees were inherently unstable for multi-branch flow distribution. The lesson: specify 45-degree branch tees with radiused entry for all multi-branch PP duct systems regardless of the $8 to $40 per-fitting cost premium. The cost of correcting a fitting selection error after installation is 30 to 100 times the upfront fitting cost saving.

PP Duct Fittings FAQ

What are PP duct fittings?
PP duct fittings are injection-molded or fabricated polypropylene components — elbows, tees, reducers, flanges, dampers, and access doors — that connect straight PP duct sections in corrosive exhaust systems. PP duct fittings provide the same chemical resistance as PP straight duct (HCl, H₂SO₄, HF, NaOH) up to 80°C. They are the connecting elements that make a complete PP ductwork ventilation system functional.

What is the difference between injection-molded and fabricated PP fittings?
Injection-molded fittings are mass-produced in standard sizes (φ20-500 mm) with tighter tolerances (±0.5 mm), smoother surfaces, and lower cost — $5 to $15 for a 250 mm elbow versus $15 to $40 for a fabricated elbow. Fabricated fittings are hand-welded from PP sheet to any size and geometry above 500 mm.

How does elbow radius affect system pressure drop?
A short-radius elbow (R=1.0D) adds 0.8 to 1.2 in. W.G. equivalent per fitting. A long-radius elbow (R=2.0D) adds 0.2 to 0.5 in. W.G. In a system with 10 elbows, long-radius elbows reduce total system pressure by 3.0 to 7.0 in. W.G. — enough to reduce fan motor size by 5 to 10 HP.

When should I use a 45-degree tee branch instead of 90-degree?
Always specify 45-degree branch tees for main duct takeoffs where flow efficiency matters. A 45-degree tee has 60 to 70 percent lower pressure drop than a 90-degree tee (0.5-1.0 in. W.G. vs 1.5-2.5 in. W.G. equivalent). Reserve 90-degree tees for short, low-flow branch connections.

What gasket material should I use for PP duct flanges?
Compressed Viton for general chemical service (HCl, H₂SO₄, HBr) up to 120°C, or PTFE for aggressive chemical service including concentrated acids and all temperatures up to 200°C. Do not use rubber gaskets — they degrade within 12 months in chemical exhaust and disintegrate into the duct.

How often should PP duct access doors be installed?
Every 50 ft of straight run, at every change of direction (elbow or tee), and immediately upstream of every damper. Minimum door size is 12 × 12 inches for ducts up to 18 inches, and 18 × 18 inches for larger ducts. Quick-open doors cost 30 to 50 percent more but save 8.7 hours of labor per year for a system with 10 doors inspected quarterly.

The correct selection of PP duct fittings — elbows, tees, reducers, flanges, dampers, and access doors — directly affects the pressure drop, installation cost, and reliability of a PP ductwork ventilation system. Specify injection-molded PP duct fittings for standard sizes up to 500 mm and fabricated fittings for larger diameters. Use long-radius elbows and 45° branch tees to minimize system pressure drop. Include access doors every 50 ft. For assistance selecting PP duct fittings for your chemical exhaust system, contact XICHENG EP LTD with your duct diameter and system data. See our PP ductwork design guide for complete system design methodology.

For the complete PP ductwork system design methodology, see our PP ductwork ventilation system design guide.





Scroll to Top

Air Emissions Solutions

XICHENG EP LTD is a professional manufacturer of industrial exhaust gas treatment equipment — wet scrubbers, activated carbon adsorption, and PP ventilation ductwork systems.

Company: 7th Floor, Building A3, No. 04, Fourth Industrial Zone, Hewan Community, Matian Street, Guangming District, Shenzhen, Guangdong 518000, China

Products

Company

Contact

xicheng023@outlook.com

☎ +86 189 2745 6906

💬 WhatsApp

Working Hours

Mon–Fri: 8:00 AM – 5:00 PM (GMT+8)

© 2024 Air Emissions Solutions — XICHENG EP LTD. All rights reserved.